The two legal designs
| Vented | Unvented (sealed) | |
|---|---|---|
| Vent area | 1 sq ft per 150 sq ft of floor; 1 per 1,500 with a Class I vapor retarder | None |
| Ground | Vapor retarder recommended / required locally | Continuous Class I vapor retarder, seams overlapped 6 in, 6 in up the wall |
| Air | Outside air | Exhaust 1 CFM / 50 sq ft, conditioned air, or dehumidification |
| Insulation | In the floor | On the walls |
Sources: Larimer County, Colorado – Community Development, updated Apr 28, 2026; International Code Council, 2018 edition. Washington State uses 1 per 300 (its own amendment, Washington State Legislature, effective Mar 15, 2024) – check your local code.
Summer and winter
In humid summers, outdoor air brought in through vents can carry more moisture than the cool crawl space can hold – one reason sealed crawl spaces became common in humid regions. Many people close vents in winter to protect pipes from freezing; if you do, the crawl space is neither properly vented nor properly sealed, so watch the humidity.
Want to stay vented? Size the vents with the vent calculator. Going sealed? Price it with the encapsulation calculator.