The rules
- Vent area (sq in) = floor area ÷ 150 × 144, or ÷ 1,500 × 144 with a Class I vapor retarder (such as 6-mil poly) on the ground, joints sealed or taped.
- Vents = vent area ÷ net free area of one vent (printed on the vent; screens and louvers reduce it).
- Openings must give cross ventilation; the model IRC allows one side without vents.
- Access: an opening of at least 18 × 24 in through the floor or 16 × 24 in through a perimeter wall (Larimer County handout).
Example (example numbers)
1,500 sq ft ÷ 150 = 10 sq ft = 1,440 sq in. With 50 sq in vents, 29 vents. With a Class I vapor retarder: 1,500 ÷ 1,500 = 1 sq ft = 144 sq in, 3 vents.
Local versions
States amend the IRC. Washington (WAC 51-51-0408) uses 1 sq ft per 300 and requires a 6-mil black polyethylene ground cover; where it allows 1/1,500, it also asks for a radon vent (Washington State Legislature, effective Mar 15, 2024). Check your building department.